PV String Voltage and Current Calculator

Check cold Voc, maximum PV currents, cable current requirements and string protection to AS/NZS 5033:2021.

Free ● Live 1 standard

Free to use. Sign up free to save, download and print.

Worked example: Appendix H.2.3, two parallel strings

Maximum array current: 22.5 A

Loading the PV String Voltage and Current Calculator…

How it works

PV string voltage, current and fuse formulas

AS/NZS 5033:2021 Cl 4.2.1.2 corrects module Voc for the expected minimum daily cell temperature. Cl 4.2.1.3.1 multiplies the corrected module voltage by the series count. Table 4.1 is an alternative for crystalline silicon without manufacturer instructions; the tool supports its printed integer bands from -40 to 24 °C.

For modules without DCUs, Cl 3.3.3.1 gives maximum string current as 1.25 × KI × Isc. Parallel strings add current. Table 4.2 determines cable current requirements from local protection. Its footnote b selects the nearest downstream sub-array device, then the array device if no sub-array protection is fitted, and total external backfeed only when neither is fitted. Table 3.1 gives string fuse bounds and the minimum ratings for sub-array and array protection. Cable sizing and installation derating need separate assessment.

Vmod max = Voc + γv × (Tmin - 25 °C)

PV array maximum voltage = Vmod max × M

Istring max = 1.25 × KI × Isc

Maximum array current = SA × Istring max

For SA > 1: string protection required when IFstring + IBF total > Imod max OCPR

String fuse: 1.2 × Istring max < In ≤ Imod max OCPR

Sub-array: In ≥ SSA × Istring max; array: In ≥ SA × Istring max

Voc, Isc
module open circuit voltage in V and short circuit current in A at STC
γv, Tmin
manufacturer Voc coefficient in V/°C per module and expected minimum daily cell temperature in °C
M, SA, SSA
modules in series, strings in the complete array and strings in the selected sub-array
KI
1 for monofacial modules; documented bifacial adjustment from Appendix J otherwise
IFstring, IBF total
other-string fault contribution, with the single-string rating floor from Cl 3.3.3.2 Note 1, and total external backfeed current in A
In, Imod max OCPR
nominal protective device current rating and module maximum series fuse / overcurrent protection rating in A

Standards

  • AS/NZS 5033:2021, Cl 3.1, Cl 3.3, Cl 4.2.1, Table 3.1 and Table 4.2

Worked example

Worked example: Appendix H.2.3, two parallel strings

AS/NZS 5033:2021 H.2.3.1 gives modules without DCUs, Isc = 9 A, KI = 1 and two parallel strings. H.2.3.2(a) calculates the combined circuit current.

StepWorkingResult
Maximum string current1.25 × 1 × 9 A11.25 A
Maximum array current2 × 11.25 A22.5 A

The informative example concerns switch disconnector selection. This calculator reproduces its current arithmetic; it does not select a switch. No module Voc, coefficient, minimum cell temperature or module fuse rating is supplied in that example, so those checks remain not assessed.

FAQ

Frequently asked questions

Not here? Ask us

Calculations run in your browser and nothing you enter is sent to a server.

How do I calculate PV string voltage in cold weather?

Use the manufacturer Voc coefficient in V/°C per module: add the coefficient times the difference between expected minimum daily cell temperature and 25 °C to module Voc, then multiply by modules in series. If the datasheet gives %/°C, convert it to V/°C per module using Voc × percentage / 100 before entering it.

When does a parallel PV string need a fuse?

Cl 3.3.4.1 requires string protection for parallel strings when the fault contribution from other strings plus total external backfeed exceeds the module maximum overcurrent protection rating. Equality does not trigger that condition. External-source protection is a separate requirement under Cl 3.3.2.

Is the cable current requirement always 1.25 times Isc?

No. That is the monofacial maximum string current. Table 4.2 also accounts for local protective device ratings, nearest downstream device ratings, other parallel strings and external backfeed. A protected cable uses its local nominal device rating. The shared Pro service also retains at least the normal maximum forward current for an unprotected cable.

What voltage limits does AS/NZS 5033:2021 specify?

Cl 3.1 limits calculated PV maximum voltage to 1000 V d.c. for domestic electrical installations and 1500 V d.c. for other installations. The PCE manufacturer maximum is a separate entered comparison. The calculator also identifies the 35 V and 120 V provisions; it does not certify a voltage safety class or the installation.

Does this calculator choose a cable size or a complete PV protection system?

It gives the minimum cable current requirement and nominal protective device bounds. Cable current capacity after installation derating, conductor size, isolation, earthing and device temperature, voltage and interrupt ratings need separate assessment. Conventional identical modules without DCUs are supported. Use Cable Sizing & Voltage Drop Pro for the cable calculation.

Do I need an account to use or share the calculator?

Calculations and copying results are free without an account. Opening an input share link is also free. Creating a share link asks for a free account.

Sign up free to keep your work.

Free to use. Saving, downloading and printing need a free account.