Generator Sizing Calculator
Size a standby or prime generator in kW and kVA from its load schedule, then check motor starts, site derating and fuel against the set's own datasheet.
Free to use. Saving and the PDF report are Pro, in the 14-day trial on every new account.
Worked example: a 10 kW comms hut on a standby set
Minimum set rating: 12.00 kW and 13.32 kVA
Loading the Generator Sizing Calculator…
How it works
Generator sizing formula: kW, kVA and power factor
A generator has two limits, the engine's output in kW and the alternator's in kVA, so a load needs a minimum of each. The real and reactive power of every item are added separately, and the apparent power in kVA is the vector sum of the two totals. That is less than adding up each item's kVA whenever the power factors differ.
For an emergency standby or prime rating, ISO 8528-1 also limits the average load over 24 hours to 70 per cent of the set's rating. A growth margin and, for UPS load, a kVA ratio from the UPS or set maker go on top when you enter them. Motor starts, altitude and temperature derating and fuel use are worked out from the set's and motor's datasheet figures, and a figure left blank is not assessed.
P = d × Σ Pᵢ
Q = d × Σ Pᵢ √(1/PFᵢ² − 1)
S = √(P² + Q²), PF = P / S
kW ≥ max(P, P₂₄ / 0.7) × (1 + m)
kVA ≥ S × r × (1 + m)
- Pᵢ, PFᵢ
- each item's real power, its quantity times its power, in kW, and its power factor, taken as lagging
- d
- share of the connected load running at once; 1 when not entered
- P, Q, S
- running real power in kW, reactive power in kvar and apparent power in kVA
- PF
- power factor of the whole load
- P₂₄
- average load over 24 hours, in kW; the 0.7 is the ISO 8528-1 limit for standby and prime ratings, and no average limit is applied to the other ratings
- r
- kVA ratio for non-linear load from the UPS or set maker; 1 when not entered
- m
- growth margin, as a fraction; 0 when not entered
Standards
- ISO 8528-1 generating set ratings (emergency standby, limited time running, prime and continuous) and the 70 % average load limit
- ISO 8528-5 performance classes G1 to G4 and their transient voltage limits
- NFPA 110 fuel classes
Worked example
Worked example: a 10 kW comms hut on a standby set
A communications hut runs a 3 kW rectifier plant at a power factor of 0.98, two 3 kW air conditioners at 0.85 and 1 kW of lighting and power at 0.9, all at once, on a standby set with a growth margin of 20 per cent.
| Step | Working | Result |
|---|---|---|
| Real power | 3 + 2 × 3 + 1 | 10.00 kW |
| Reactive power | 3 × 0.203 + 6 × 0.620 + 1 × 0.484 | 4.81 kvar |
| Apparent power | √(10.00² + 4.81²) | 11.10 kVA |
| Power factor | 10.00 / 11.10 | 0.90 |
| Minimum set rating | 10.00 × 1.2 and 11.10 × 1.2 | 12.00 kW and 13.32 kVA |
For a standby or prime set, ISO 8528-1 also limits the 24 hour average to 70 per cent of the rating: a 6 kW average needs 6 ÷ 0.7 = 8.57 kW, so here the running load sets the size. Adding each item's kVA instead gives 11.23 kVA, which overstates the load because the power factors differ. The set's motor starting kVA and its derating for the site come from its datasheet.
FAQ
Frequently asked questions
Not here? Ask us
Calculations run in your browser and nothing you enter is sent to a server.
What size generator do I need?
Add up the real power of everything that runs at once, in kW, and its reactive power, in kvar, from each item's power factor; the apparent power is √(kW² + kvar²), in kVA. The set needs a kW rating of at least the running kW and a kVA rating of at least the running kVA, each with any growth margin, and for a standby or prime set the 24 hour average must stay within 70 per cent of the kW rating (ISO 8528-1). Then check the largest motor start against the set's published starting kVA, and the site derating from its datasheet.
How do I convert kVA to kW?
Multiply by the power factor: kW = kVA × PF, and kVA = kW ÷ PF. A 3 kW air conditioner at a power factor of 0.85 draws 3.53 kVA. For a whole load, add the kW and kvar of each item first and take √(kW² + kvar²), because adding each item's kVA overstates the total when the power factors differ. A set's datasheet gives its kW and kVA ratings separately, and the tool checks each one.
Why is a generator rated in kVA as well as kW?
A generator has two limits: the engine, in kW, and the alternator, in kVA. A load needs both, so the tool gives a minimum for each and checks your set's datasheet ratings against them separately.
How does motor starting affect the size?
A motor started direct on line draws its locked rotor current, several times its running current, and the generator voltage dips while it does. Set makers publish how many starting kVA a set can supply at a given dip. The tool works out the motor's starting kVA from its nameplate and starter and checks it against that figure. On many comms sites the air conditioner start, not the steady load, decides the set.
Why does a UPS need a larger generator?
A UPS that draws non-linear current distorts the generator voltage and heats the alternator, so the alternator may need to be larger than the UPS kW alone suggests. How much larger depends on the UPS and the set, so the tool takes the kVA ratio from the UPS or set maker rather than assuming one.
How much output do altitude and temperature cost?
Both reduce output because the engine has less dense air to burn fuel with. How much depends on the engine, its aspiration and its rating, so the tool uses the derating from the set's datasheet rather than a typical value.
Save your work with 14 days of Pro.
Free to use. The PDF report and the catalogue are Pro too. No credit card.