Earth Fault Loop Impedance Calculator

Find the maximum Zs for a protective device, or check a circuit from Ze and its active and earth conductors.

Free ● Live 2 standards

Free to use. Sign up free to save, download and print.

Worked example: C32 on 6 mm² TPS over 25 m

Earth fault current at load: 371.555 A

Loading the Earth Fault Loop Impedance Calculator…

How it works

Earth fault loop impedance formula and maximum Zs

Cl 5.7.4 requires Zs × Ia ≤ U₀. Table 8.1 gives printed examples at 230 V to earth using approximate mean tripping currents. These printed values take precedence over recalculation. For an unlisted MCB rating up to 200 A, Appendix B4.5 gives Ia as 4 × In for Type B, 7.5 × In for Type C and 12.5 × In for Type D. MCB ratings above 200 A and unlisted fuses need manufacturer device data and are not assessed here.

Actual circuit Zs uses the AS/NZS 3008.1.1:2025 a.c. resistance at the selected conductor temperature, 75 °C for PVC or 90 °C for XLPE, and the cable reactance. Ze is treated as resistive, as in the Pro loop check. The Table 5.1 copper earth minimum is assumed when no earth size is entered; an entered copper earth is checked against that minimum, Cl 5.3.3.1.2. Fault duty needs a separate check. Confirm the protective device time/current curve because Table 8.1 uses mean values.

Zs,max = printed Table 8.1 cell, or U₀ / Ia for an unlisted MCB

Ia = k × In, k = 4 (B), 7.5 (C), 12.5 (D)

Rc = (Ra + Rpe) × L / 1000, Xc = (Xa + Xpe) × L / 1000

Zs = √((Ze + Rc)² + Xc²), Zs ≤ Zs,max

Earth fault current at load = U₀ / Zs

Maximum route length = L at which Zs = Zs,max, the same formula solved for L

U₀
nominal phase-to-earth voltage, fixed at 230 V
Ia, In
approximate mean trip current and device rated current, in A
Ze
external earth loop impedance at the circuit origin, in Ω, treated as resistive
Ra, Rpe, Xa, Xpe
active and earth conductor resistance and reactance, in Ω/km
L
one-way route length, in m, with one active and one earth conductor
Rc, Xc, Zs
cable loop resistance, cable loop reactance and total loop impedance, in Ω

Standards

  • AS/NZS 3000:2018 Table 8.1 and notes, Cl 5.7.2 to 5.7.4, Appendix B4.4 and B4.5, Table 5.1
  • AS/NZS 3008.1.1:2025 cable resistance and reactance tables

Worked example

Worked example: C32 on 6 mm² TPS over 25 m

Example inputs: an MCB Type C rated 32 A, the 0.4 s condition, 230 V to earth, Ze = 0.30 Ω and a 25 m one-way run of 6 mm² copper 2-core and earth TPS with PVC at 75 °C. Leave the earth size blank.

StepWorkingResult
Earth usedTable 5.1, 6 mm² copper active2.5 mm² copper
Maximum ZsPrinted Table 8.1, Type C, 32 A1.0 Ω
Cable loop resistance(3.75 + 9.01) × 25 / 10000.319 Ω
Cable loop reactance(0.0967 + 0.102) × 25 / 10000.0049675 Ω
Actual Zs√((0.30 + 0.319)² + 0.0049675²)0.61902 Ω
Loop check0.61902 ≤ 1.0Within limit
Earth fault current at load230 / 0.61902371.555 A

Resistance comes from AS/NZS 3008.1.1:2025 Table 4.7(A), 75 °C, and reactance from Table 4.1(B), multicore PVC. Ze and route length are named example inputs. This is a loop check against the mean-current limit; confirm the device curve and the installed earth separately.

FAQ

Frequently asked questions

Not here? Ask us

Calculations run in your browser and nothing you enter is sent to a server.

What is the maximum Zs for a C32 circuit-breaker?

AS/NZS 3000:2018 Table 8.1 prints 1.0 Ω for a Type C MCB rated 32 A at 230 V to earth. The tool uses that printed cell. Recalculating 230 / (7.5 × 32) gives an unrounded method value, which does not replace the printed limit.

When do I use 0.4 s or 5 s?

Cl 5.7.2(a) specifies 0.4 s for final subcircuits supplying socket-outlets rated up to 63 A, hand-held Class I equipment or portable equipment intended for manual movement during use. Cl 5.7.2(b) permits 5 s for other circuits where safe touch voltages are demonstrated. The tool requires confirmation for 5 s. Table 8.1 Note 3 bases MCB cells on instantaneous operation within 0.1 s, so those cells serve both conditions; fuse limits depend on the chosen time.

Can I enter a device rating that is not in Table 8.1?

For an unlisted MCB Type B, C or D rating up to 200 A, the tool calculates 230 / (k × In) using the Appendix B4.5 mean multipliers 4, 7.5 and 12.5, and labels the result as the Table 8.1 method rather than a printed cell. MCB ratings above 200 A need manufacturer device data and are not assessed. Unlisted fuses are not assessed, and fuse cells are never interpolated.

What earth conductor size is used if I leave it blank?

The Pro earth-sizing service selects the Table 5.1 copper minimum for the active size and material. Multicore selections use its integrated-earth method; single-core selections use its separate-earth method, including the mechanical minimum. Enter the installed earth size and material when known. An entered copper earth below the Table 5.1 minimum shows an earth size fail beside the Zs result; a smaller earth needs a Cl 5.3.3.1.3 calculation. Fault duty is not checked.

Does this use cold conductor resistance or replace an earth loop test?

The circuit calculation uses the same a.c. resistance and reactance as Pro, at 75 °C for PVC or 90 °C for XLPE. It adds Ze as a resistive source term and includes cable reactance. It does not calculate a cold d.c. resistance test limit or model parallel circuits, d.c. sources or an RCD trip curve. Table 8.1 uses approximate mean tripping currents, so confirm the device curve and verify the installation separately.

Sign up free to keep your work.

Free to use. Saving, downloading and printing need a free account.