Earth Electrode Resistance Calculator
Also known as Earthing & Lightning Protection Calculator
Earth electrode resistance for rods, strips and grids, with lightning risk, rolling sphere, bonding and surge checks for a communications site.
Free to use. Sign up free to save, download and print.
Worked example: 2.4 m rods to reach 10 Ω in 100 Ω·m soil
Six rods, λ = 2.87: 9.3 Ω
Loading the Earth Electrode Resistance Calculator…
How it works
Earth rod resistance formula
The resistance of an earth electrode is the resistance between it and remote earth, and the soil sets most of it. It rises in direct proportion to the soil resistivity, so a measured resistivity matters more than any other input. A longer rod lowers it a good deal and a thicker one only a little.
For one driven rod the calculator uses the Dwight equation given in IEEE 142. Several rods together give a higher resistance than one rod divided by their number, because each sits in the potential field of the others, so for rods in a line or around a hollow square it uses the BS 7430 method, which adds that mutual resistance through a factor λ from its tables for the layout and the number of rods.
R = ρ / (2πL) × (ln(8L / d) − 1)
Rₙ = R (1 + λα) / n
α = ρ / (2πRs)
- R
- resistance of one rod, in Ω
- ρ
- soil resistivity, in Ω·m
- L, d
- rod length and diameter, in metres
- Rₙ
- resistance of n equal rods together, in Ω
- s
- spacing between neighbouring rods, in metres
- λ
- BS 7430 factor for the layout and the number of rods: 2 to 10 rods in a line, or a hollow square
- α
- spacing factor, with no unit
Standards
- IEEE 142 (Dwight equation) for driven rod resistance
- BS 7430 for rod arrays and horizontal strip resistance
- IEC 62305-3 cl. 5.4.1 and ITU-T K.112 cl. 6.1, the recommended earth resistance below 10 Ω for a lightning protection system
- IEEE 80 for grid resistance and tolerable touch and step voltages
- IEC 62305-2 damage probabilities for a simplified lightning risk screen (not the AS/NZS 1768:2021 risk assessment)
- IEC 62305-1 and IEC 62305-3 for protection levels, rolling sphere, down conductors, separation distance and conductor sizes
- ITU-T K.27 bonding configurations for telecommunication buildings
- IEC 61643-11 and IEC 61643-21 surge protective devices, and IEC 60364-4-44 impulse withstand for mains equipment
Worked example
Worked example: 2.4 m rods to reach 10 Ω in 100 Ω·m soil
Earth rods 2.4 m long and 16 mm in diameter, driven in a line 3 m apart in soil of 100 Ω·m, for the 10 Ω that IEC 62305-3 recommends for a lightning protection earth.
| Step | Working | Result |
|---|---|---|
| Shape term | ln(8 × 2.4 / 0.016) − 1 | 6.09 |
| One rod | 100 / (2π × 2.4) × 6.09 | 40.4 Ω |
| Spacing factor α | 100 / (2π × 40.4 × 3) | 0.131 |
| Five rods, λ = 2.54 | 40.4 × (1 + 2.54 × 0.131) / 5 | 10.8 Ω |
| Six rods, λ = 2.87 | 40.4 × (1 + 2.87 × 0.131) / 6 | 9.3 Ω |
Six rods are the fewest in a line that reach 10 Ω. They give 9.3 Ω, not the 6.7 Ω that 40.4 Ω divided by six would suggest, because each rod sits in the field of the others. Every figure scales with the soil resistivity, so the same six rods in 200 Ω·m soil give 18.5 Ω.
FAQ
Frequently asked questions
Not here? Ask us
Calculations run in your browser and nothing you enter is sent to a server.
What earth resistance should I aim for on a communications site?
It depends on the project. IEC 62305-3 cl. 5.4.1 (as reproduced by DEHN) and ITU-T K.112 cl. 6.1 recommend an earth below 10 Ω for a lightning protection system where it can be reached. It is a recommendation, not a pass mark: an electrode that meets the minimum length or ring radius for its protection class is the alternative. Tighter targets come from the client or the network operator. The tool lets you set the target and shows what electrode it takes to reach it, and the installed resistance should always be confirmed by measurement.
How do you calculate the resistance of an earth rod?
With the Dwight equation given in IEEE 142, R = ρ / (2πL) × (ln(8L/d) − 1), where ρ is the soil resistivity in Ω·m and L and d are the rod length and diameter in metres. A single 2.4 m rod of 16 mm diameter in 100 Ω·m soil works out at 40.4 Ω. The equation takes the soil as uniform, so confirm the installed rod by measurement.
Is a longer earth rod better than a thicker one?
Yes, by a wide margin. In 100 Ω·m soil a 2.4 m rod of 16 mm diameter is 40.4 Ω. Doubling its length to 4.8 m brings that to 22.5 Ω, while doubling its diameter to 32 mm only brings it to 35.8 Ω, because the diameter appears only inside the logarithm of the Dwight equation.
Why does adding rods not divide the resistance by the number of rods?
Because the rods are not independent. Each rod sits in the potential field of the others, so an array has a higher resistance than a simple division suggests. The tool uses the BS 7430 method, which adds the mutual resistance between rods through a factor for the layout, so efficiency falls as rods get closer together or more numerous.
How is a Wenner four-pin survey reduced to a resistivity?
The apparent resistivity is ρ = 2πaR, where a is the equal probe spacing and R is the measured resistance. The result represents the soil to a depth of roughly the probe spacing. Readings at several spacings show how resistivity changes with depth, which matters when a deep rod passes through a lower resistivity layer.
Is the lightning risk a full IEC 62305-2 assessment?
No. The risk mode is a simplified screen: it compares the expected number of direct strikes with your tolerable frequency and picks the lowest protection level whose IEC 62305-2 damage probability brings the damaging strikes within it. It shows quickly whether protection is needed and at roughly what level. The final protection measures should come from a full risk assessment to AS/NZS 1768 or IEC 62305-2.
Sign up free to keep your work.
Free to use. Saving, downloading and printing need a free account.