Cable Short-Circuit Withstand Calculator
Check a conductor against fault current and clearing time or the device's total let-through I²t, with the K value and temperature basis shown.
Free to use. Sign up free to save, download and print.
Worked example: 10 kA for 1 s, Appendix A.9
Maximum RMS current for 1 s: 10 564 A
Loading the Cable Short-Circuit Withstand Calculator…
How it works
Cable short-circuit withstand formula
AS/NZS 3008.1.1:2025 Cl 5.3 uses an adiabatic calculation: heat loss during the fault is neglected. Table 5.1 gives K for the conductor material and initial and final temperatures. The temperature limits apply for durations up to 5 s.
For clearing-time data, S must be at least Smin. With manufacturer let-through data, K²S² must be greater than I²t under AS/NZS 3000:2018 Cl 2.5.4.2 Note 2, so equality fails. The minimum area uses K for the entered size; recalculate after changing a PVC size across 300 mm².
I²t = K²S²
Smin = √(I²t) / K
Imax = KS / √t
For manufacturer let-through: K²S² > I²t
- I
- fault current, RMS over the fault duration, in A
- t
- device fault duration in s, up to 5 s
- S, Smin
- entered and minimum conductor cross-sectional areas in mm²
- K
- material and temperature constant in A√s/mm²
- I²t
- current squared times duration, or manufacturer total let-through energy in A²s
Standards
- AS/NZS 3008.1.1:2025 Cl 2.3.3, Cl 5.2 and 5.3, Tables 3.1, 5.1 and 5.2, Appendix A.9
- AS/NZS 3000:2018 Cl 2.5.4.2 Note 2, manufacturer let-through energy for very short faults and current limiting devices
Worked example
Worked example: 10 kA for 1 s, Appendix A.9
AS/NZS 3008.1.1:2025 A.9.1 and A.9.2(a): copper PVC at 75 °C initially and 160 °C finally, compression joints, 10 000 A and 1 s. Check a 95 mm² conductor.
| Step | Working | Result |
|---|---|---|
| K from Table 5.1 | Copper, 75 to 160 °C | 111.2 A√s/mm² |
| Fault duty | 10 000² × 1 | 100 000 000 A²s |
| Minimum area | √(100 000 000) / 111.2 | 89.9 mm² |
| Entered size | 95 mm² ≥ 89.9 mm² | PASS |
| Maximum RMS current for 1 s | 111.2 × 95 / √1 | 10 564 A |
Appendix A.9 selects 95 mm² for PVC. Its X-90 example uses K = 142.9, from 90 to 250 °C, giving 70.0 mm² and selecting 70 mm². This is a conductor thermal check; assess other cable components and installation restraints separately.
FAQ
Frequently asked questions
Not here? Ask us
Calculations run in your browser and nothing you enter is sent to a server.
How do I calculate the minimum cable size for a short circuit?
Use Smin = √(I²t) / K with current in A, time in s and area in mm². K depends on the material and temperature limits. Select an appropriate conductor size and check it again, because the PVC temperature limit changes above 300 mm². This calculator checks thermal withstand at the maximum prospective fault current.
Which K value does the calculator use?
K comes from AS/NZS 3008.1.1:2025 Table 5.1. V-75 and V-90 start at 75 °C on the 75 °C rating basis, Cl 3.3.1.3, Table 3.1 and A.9.2(a)(i). A V-90 cable operated at 90 °C can be set to start at 90 °C instead (copper K 99.7 up to 300 mm²). The supported cross-linked types start at 90 or 110 °C. Table 5.2 gives PVC a final limit of 160 °C up to 300 mm² and 140 °C above it, and the supported cross-linked types 250 °C.
When must I use the device manufacturer's I²t?
Use total let-through I²t for current limiting devices and durations below 0.1 s, as required by AS/NZS 3000:2018 Cl 2.5.4.2 Note 2. Use data at the entered maximum prospective fault current. The conductor's K²S² must be greater than that energy; equality fails.
What fault durations can I enter?
Clearing-time mode accepts 0.1 s to 5 s inclusive. I²t mode accepts a positive duration up to 5 s, including below 0.1 s. Duration is required in both modes to enforce the temperature-limit scope in AS/NZS 3008.1.1:2025 Cl 5.2 and to calculate the maximum permissible RMS current.
What does a PASS cover?
PASS covers conductor thermal withstand for the entered duty at the maximum fault current, for cable rated up to 0.6/1 kV. Check the minimum fault current and device clearing time separately. Sheaths, bedding, joints and mechanical restraint require separate assessment under Tables 5.3 and 5.4 and Cl 5.4. Cl 5.2 also calls for lower thermoplastic temperature limits where pressure points cannot be avoided; this calculator does not apply that adjustment.