Maximum Demand Calculator
Calculate demand per phase from the supplied loads, with the table, row, column or clause behind each contribution.
Free to use. Sign up free to save, download and print.
Worked example: single domestic demand of 84.4 A
Maximum demand: 84.391304 A, rounded to 84.4 A
Loading the Maximum Demand Calculator…
How it works
Maximum demand calculation using Appendix C
AS/NZS 3000:2018 Appendix C is informative. Tables C1 and C2 apply their load group allowances once per installation and phase, then add those contributions to obtain the phase demand. The largest phase total is the maximum demand.
Table C3 converts area demand in VA to current using the entered supply voltage. Table C4 applies a switchboard diversity factor to circuit overload ratings. Table C5 covers fixed domestic cooking appliances on a final subcircuit, while C2.5.2 covers arc and resistance welding machines.
Size the consumer mains for this demand in Cable Sizing & Voltage Drop
I_phase = sum of assessed load group currents on that phase
I_max = max(I_A, I_B, I_C)
Single-phase kW input: I = 1000 × P / (V_LN × PF)
Balanced three-phase area demand: I = area × rate / (sqrt(3) × V_LL)
- I
- current in A, before any applicable load group allowance in the kW conversion
- P, PF
- equipment input power in kW and its entered power factor
- V_LN, V_LL
- entered phase-to-neutral and line-to-line supply voltages in V
- area, rate
- floor area in m² and chosen energy demand in VA/m²
Standards
- AS/NZS 3000:2018, Appendix C Tables C1 to C5 and C2.5.2
Worked example
Worked example: single domestic demand of 84.4 A
Appendix C Example 1, C2.3.2.1, pages 462 to 463: a 230 V single-phase installation with 24 lighting points, 10 m of track, a 50 W exhaust fan, nine single and eight double 10 A socket-outlets, a 1000 W strip heater, a 15 A socket-outlet, a 10 000 W range, a 4800 W storage water heater and 3000 W of tennis court lighting.
| Step | Working | Result |
|---|---|---|
| Lighting, Table C1 (a)(i), Column 2 | 24 + 2 × 10 + 1 = 45 points; 3 + 2 × 2 | 7 A |
| Outdoor lighting, (a)(ii) | 3000 / 230 × 0.75 | 9.782609 A |
| Socket-outlets and strip heater, (b)(i) | 9 + 2 × 8 + 1 = 26 points; 10 + 5 | 15 A |
| 15 A socket-outlet, (b)(ii) | One addition under Table C1 Note 10 | 10 A |
| Range, (c) | 10000 / 230 × 0.50 | 21.739130 A |
| Storage water heater, (f) | 4800 / 230 | 20.869565 A |
| Maximum demand | 7 + 3000 / 230 × 0.75 + 15 + 10 + 10000 / 230 × 0.50 + 4800 / 230 | 84.391304 A, rounded to 84.4 A |
The calculation keeps full precision until the final display. The printed example rounds individual entries; both give 84.4 A to one decimal place.
FAQ
Frequently asked questions
Not here? Ask us
Calculations run in your browser and nothing you enter is sent to a server.
Is this maximum demand calculator free?
Yes. Use every calculation method without an account and copy the working. Creating a share link needs a free account; opening one does not.
Which domestic installation method should I use?
Use Table C1 and choose single or multiple domestic installations. For multiple installations, enter the living units supplied on each phase and the affected unit count for each relevant appliance group. Appliance quantities and affected living units are separate entries.
Can I apply Table C5 to consumer mains?
Table C5 is for fixed domestic ranges, ovens and hotplates on a final subcircuit. Tables C1 to C4 cover consumer mains and submains. Cooking loads on domestic consumer mains use the applicable Table C1 group.
How do the area and switchboard methods work?
Table C3 multiplies each floor area by an explicitly chosen published VA/m² rate, then converts to current. EV charging is additional to other area demand. Table C4 requires switchboard conformity with AS/NZS 61439 and counts downstream circuit-protection devices across the switchboard, counting each multi-pole device once.
What happens when a load is incomplete or needs separate assessment?
The result stays not assessed and gives a reason. A known subtotal is not shown as the completed maximum demand. Loads excluded by an explicit table rule are identified in the working.
Does the calculator size cables or protective devices?
It provides the demand current and working. Cable Sizing & Voltage Drop is the related Pro tool for cable selection, voltage drop and the further circuit checks.