Rack Heat Load Calculator

Also known as Rack Heat Load Designer

Turn a rack's equipment draws into a heat load in watts and BTU/hr, then size the airflow and cooling it needs.

Free ● Live 4 standards

Free to use. Sign up free to save, download and print.

Worked example: a 1.37 kW radio cabinet at a 10 °C rise

Airflow for a 10 °C rise: 409 m³/h (241 CFM)

Loading the Rack Heat Load Calculator…

How it works

Rack heat load formula: watts to BTU/hr and airflow

A rack's heat load is the power its equipment draws, because communications and IT equipment turn nearly all of their input power into heat. Each line is its quantity times the datasheet draw, and a transmitter keyed part of the time counts at its idle draw plus the keyed share of the difference. In BTU/hr the load is 3.412142 times the watts, the NIST SP 811 conversion.

Air carries that heat away. The sensible heat equation gives the volume of air that removes the load at a chosen rise from inlet to outlet, for dry air at 20 °C and sea level pressure: 1.2 kg/m³ and a specific heat of 1005 J/(kg·K), worked out from the gas constant, molar mass and ratio of specific heats of the U.S. Standard Atmosphere 1976 (1.204 and 1004.7 exactly; the rounding gives 0.3 per cent more air). Thinner air at altitude carries less heat in each cubic metre, so the volume is divided by the air density ratio of the ISO 2533 standard atmosphere.

P = Σ n × (Pᵢ + (Pₖ − Pᵢ) × d)

BTU/hr = 3.412142 × P

Q = 3600 × P ÷ (ρcₚ × ΔT × σ), with ρcₚ = 1206 J/(m³·K)

CFM = Q ÷ 1.69901

σ = (1 − 2.25577 × 10⁻⁵ × z)^4.2559

P
heat load, in watts
n
quantity on a schedule line
Pₖ, Pᵢ
draw of one unit keyed or at full load, and idle, in watts, from the datasheet
d
share of the time keyed, 0 to 1; 1 for equipment that draws continuously
Q
airflow, in m³/h; Q ÷ 3.6 gives L/s
ΔT
temperature rise from inlet to outlet, in °C, which is the same rise in kelvin
ρcₚ
heat carried by a cubic metre of dry air at 20 °C and sea level pressure for each degree: 1.2 kg/m³ × 1005 J/(kg·K)
σ, z
air density at the site as a share of sea level, 1 at sea level, and the site altitude in metres

Standards

  • ASHRAE TC 9.9 Thermal Guidelines for Data Processing Environments, 5th edition (2021): recommended and allowable inlet temperature ranges for classes A1 to A4 and H1
  • IEC TR 60890 surface factors for the effective cooling surface of an enclosure
  • NIST SP 811 conversions (W to BTU/hr, tons of refrigeration, CFM) and the ISO 2533 standard atmosphere for altitude

Worked example

Worked example: a 1.37 kW radio cabinet at a 10 °C rise

A cabinet at sea level holds four base station transmitters that draw 300 W keyed and 60 W idle and are keyed half the time, a 150 W switch and two 250 W servers, with the air rising 10 °C from inlet to outlet.

StepWorkingResult
Transmitters4 × (60 + (300 − 60) × 0.5)720 W
Heat load720 + 150 + 2 × 2501,370 W
In BTU/hr1370 × 3.4121424,675 BTU/hr
Airflow for a 10 °C rise3600 × 1370 ÷ (1206 × 10)409 m³/h (241 CFM)

Halving the rise to 5 °C doubles the airflow to 818 m³/h. At a site 1,000 m up the air is 90.75 per cent as dense as at sea level, so the same cabinet needs 10.20 per cent more air, 451 m³/h. These are sensible heat figures for the air through the cabinet: recirculation, bypass and latent load are not modelled.

FAQ

Frequently asked questions

Not here? Ask us

Calculations run in your browser and nothing you enter is sent to a server.

How do I convert watts to BTU/hr?

Multiply the watts by 3.412142, the NIST SP 811 conversion, which follows from 1 BTU/hr being 0.2930711 W with the International Table BTU. So 1 kW is 3,412 BTU/hr and a 1,370 W cabinet is 4,675 BTU/hr. To go the other way, divide by 3.412142. A ton of refrigeration is 12,000 BTU/hr, or 3,516.85 W.

How is the heat load worked out?

For each line, the quantity is multiplied by the power draw; for a transmitter keyed part of the time, by its idle draw plus the keyed share of the difference. The lines are added together. Communications and IT equipment turn nearly all of their input power into heat, so the total power is taken as the heat load. It is then converted to kilowatts, BTU/hr and tons of refrigeration.

How much cooling does a rack need?

At least its heat load in sensible cooling: a rack drawing 1,370 W needs 1,370 W, or 4,675 BTU/hr, taken out. A design margin is your own policy, not a standard figure, so the tool adds one only if you set it. With N+1 or N+2, one or two standby units are added to the N units that share the duty, each sized for the design load divided by N: with two duty units and N+1, that rack needs three units of 685 W, 2,055 W installed. Latent load and the cooling unit's derating are not included; take them from its datasheet.

Why does altitude change the airflow?

Air is less dense at altitude, so each cubic metre carries less heat. To remove the same heat at the same temperature rise, more air has to move. The tool uses the International Standard Atmosphere to estimate air density at the site altitude and shows how much the airflow increases.

What does the ASHRAE check tell me?

The ASHRAE TC 9.9 Thermal Guidelines, 5th edition (2021), give a recommended inlet temperature range for IT equipment and a wider allowable range for each equipment class. The recommended range is 18 to 27 °C for classes A1 to A4 and 18 to 22 °C for the high density class H1. The allowable ranges are 15 to 32 °C for A1, 10 to 35 °C for A2, 5 to 40 °C for A3, 5 to 45 °C for A4 and 5 to 25 °C for H1. The tool shows whether your inlet temperature is in the recommended range, in the allowable range for the chosen class, or outside it, and how much headroom is left. It checks the dry bulb temperature only; humidity and dew point limits are listed but not checked.

How is a sealed enclosure assessed?

A sealed cabinet sheds heat through its walls and roof. The tool works out the effective surface area with the IEC TR 60890 surface factors, multiplies it by the enclosure maker's heat transfer coefficient and by the allowed temperature difference, and compares the result with the internal heat load plus any solar gain. If the walls cannot shed enough heat, it checks whether outside air is cool enough for forced ventilation, and otherwise sizes the active cooling needed.

Sign up free to keep your work.

Free to use. Saving, downloading and printing need a free account.