Load: equipment heat roll-up
Build the cabinet equipment schedule as named rows of quantity, typical per-device draw, and a transmit/utilisation duty cycle. The tool rolls the heat up to the total in watts, kilowatts, and BTU/hr, the ton-of-refrigeration equivalent, and the average W/U density over the selected rack height (12U, 24U, 42U, or 47U). The roll-up assumes equipment dissipates approximately 100 percent of its input power as heat, with the per-line duty cycle scaling TX equipment that is not keyed continuously to its average keyed load (left at 100 percent for continuous gear). A labelled typical-equipment-heat reference table (switch, router, server, base station, amplifier, UPS, PDU, patch panel) is provided for sanity-checking; passive items such as patch panels and fibre trays dissipate effectively no heat.
Airflow: ventilation sizing with altitude derate
Airflow mode sizes the ventilation volume needed to hold a chosen inlet-to-outlet temperature rise for the rack heat load, using the sensible-heat equation (Q in m³/h = P × 3600 / (1206 × ΔT in °C), and CFM = BTU/hr / (1.08 × ΔT in °F)). Results are reported in m³/h, CFM, and L/s, with an airflow-versus-ΔT table for quick what-if comparison. A site-altitude input applies an ISA air-density derate: thinner air at altitude carries less heat per unit volume, so the required volume scales up, and both the sea-level and altitude-corrected figures are shown along with the percentage uplift.
Cooling: refrigeration capacity sizing
Cooling mode sizes the installed cooling capacity from the heat load, a design margin, and a redundancy scheme. Installed capacity is heat load × (1 + design margin) × redundancy factor, where N+1 and N+2 scale the installed plant by (n+1)/n and (n+2)/n over the number of units sharing the duty. Results are reported in kW, tons of refrigeration, and BTU/hr, with the per-unit duty and a side-by-side N, N+1, N+2 comparison table. This is sensible-capacity sizing; latent load and unit derating must be confirmed against the CRAC or split-system datasheet.
Climate: ASHRAE TC9.9 envelope check
Climate mode checks the cold-aisle inlet temperature against the ASHRAE TC9.9 thermal guidelines. The recommended band of 18-27 °C applies to all classes; each class adds a wider allowable dry-bulb envelope (A1 15-32 °C, A2 10-35 °C, A3 5-40 °C, A4 5-45 °C). The tool classifies the inlet as Recommended, Allowable, or Exceeds, colours the headline card accordingly, and reports the headroom in degrees to both the recommended maximum and the selected class allowable maximum.
Enclosure: sealed outdoor cabinet assessment
Enclosure mode assesses a sealed outdoor cabinet (IP/NEMA) where heat is shed through the enclosure surface rather than by through-flow air. It computes the effective dissipating area from the cabinet dimensions and mounting (free-standing or wall-mounted) per IEC 60890, and the passive dissipation capability Q = k × A × ΔT, where k is the still-air combined convection and radiation coefficient for the surface material (painted steel 5.5, stainless 3.7, aluminium 12, polyester 3.5 W/m²K). Comparing the internal heat load plus any solar gain against the passive capability, the tool returns a verdict on a decision ladder: sealed passive (with the resulting internal temperature), forced ventilation (with the required airflow, only viable when ambient is below the allowable internal temperature), or active cooling (with the required capacity in kW).
Import from the Rack Layout Designer
In Load mode the equipment schedule can be imported directly from a saved or currently-open Rack Layout Designer cabinet. The placed items are aggregated by equipment type into named rows of quantity and per-device draw, so the cabinet contents are not re-keyed. Passive items (zero watts) are kept so the schedule mirrors the rack. After import the schedule is fully editable, including the per-line duty cycle.
Per-mode reference tables and charts
Each mode carries its own reference table and chart: the typical-equipment-heat table in Load, the airflow-versus-ΔT comparison in Airflow, the N / N+1 / N+2 capacity comparison in Cooling, and the ASHRAE recommended and allowable bands in Climate. The result canvas pairs a headline conversion (for example kW alongside BTU/hr) with a derived-metrics grid so the key figure and its supporting numbers are read together.
Honest modelling and clipboard output
Every figure is a modelled estimate derived from a standard textbook constant (1 W = 3.412 BTU/hr, 1 ton = 3.517 kW = 12 000 BTU/hr, the 1.08 sensible-heat constant, the 1206 J/m³K volumetric heat capacity of air, and the ISA density model), anchored to user-entered equipment draw. Typical equipment heat figures are labelled as typical class values to be verified against the nameplate. The active mode result block copies to the clipboard in a spreadsheet-friendly format, and the equipment schedule and parameters persist in localStorage between sessions.
Browser-based, client-side computation
All computation runs entirely in your browser with no backend. The equipment schedule, mode parameters, and results never leave the machine. Useful where equipment lists and site thermal data are commercially confidential, and convenient for working offline on a site walk or in a remote shelter.